Huawei HCSP-Field-Data Center Facility V1.0 H20-923_V1.0 Dumps in PDF

Free Huawei H20-923_V1.0 Real Questions (page: 9)

On the ECC800-Pro WebUI, the PUE configuration mode can be "Standard" or "User-defined".

  1. True
  2. False

Answer(s): A

Explanation:

Huawei’s ECC800-Pro supports PUE (Power Usage Effectiveness) management as part of its energy efficiency and green data center features. In practical O&M, different sites calculate PUE differently depending on metering topology, what loads are included (IT load only vs. auxiliary loads), and whether the site uses integrated modules (UPS, cooling, lighting, etc.) or external systems. To handle these real-world differences, the ECC800-Pro provides two PUE configuration approaches on the WebUI. “Standard” mode is used when the site’s metering points and calculation logic align with a predefined Huawei template, enabling rapid commissioning and consistent reporting. “User-
defined” mode is used when the customer’s metering structure or management requirements differ—allowing engineers to select specific measurement points, define inclusion/exclusion rules, and tailor the calculation path so that displayed PUE matches the site’s accepted KPI definition. This dual-mode design ensures PUE is both standardized where possible and flexible where necessary, improving energy analysis accuracy and supporting optimization actions.



The NetEco service program backend can be accessed through the iBMC port.

  1. True
  2. False

Answer(s): B

Explanation:

In Huawei data center facility management, NetEco is the management software platform (server/application) used to centrally monitor and manage sites, while iBMC is the out-of-band hardware management interface used for server remote maintenance (such as power control, hardware health, BIOS settings, and remote console) on the specific server where iBMC exists. The iBMC port is not a service access interface for NetEco. NetEco’s backend services are accessed through the server operating system network interfaces (management/service network) and corresponding application ports after the server is properly networked and configured. Even if NetEco is deployed on a Huawei server that has iBMC, iBMC only provides a channel to manage the server hardware and does not expose NetEco application access as an official commissioning/O&M path. Therefore, NetEco backend access should be planned via the site’s management network (IP addressing, routing, security policy), not via iBMC.



The NetEco northbound interface does not support the SNMP protocol. Only WebService interfaces are supported.

  1. True
  2. False

Answer(s): B

Explanation:

In Huawei’s data center facility management architecture, the northbound interface of NetEco is designed specifically to integrate with upper-layer systems such as enterprise NMS platforms, SOC/monitoring centers, and customer unified O&M systems. To meet common industry integration practices, NetEco northbound capabilities are not limited to only one interface type. In addition to WebService-style interfaces used for richer data exchange and structured integration, NetEco also supports SNMP-based northbound integration, which is widely used for alarm forwarding, basic status monitoring, and interoperability with standard network management tools. SNMP is particularly common in mixed-vendor environments because it enables a lightweight and standardized method to deliver key alarms and events to a customer’s central monitoring platform without requiring deep application coupling. Therefore, the statement that “only WebService interfaces are supported and SNMP is not supported” is incorrect: NetEco northbound integration supports SNMP along with other northbound interface methods depending on the integration scenario and customer requirements.



Through device management, you can view the information about

  1. Overview
  2. Alarm
  3. Signal
  4. Service period

Answer(s): A,B,C,D

Explanation:

In Huawei smart module management (such as on the ECC800-Pro/WebUI), Device Management is used to centrally view and maintain managed objects (UPS, SmartLi, rPDU, sensors, air conditioners, etc.). The Overview page provides a consolidated snapshot of a device’s operating status, key parameters, running mode, and basic identification information so engineers can quickly judge whether the device is healthy and online. The Alarm view lists active and historical alarms related to the device, supporting rapid fault isolation and verification after recovery. The Signal view shows monitoring points and I/O status (including analog values and digital inputs/outputs where applicable), which helps engineers confirm sensor wiring, linkage logic, and real-time state changes during commissioning and troubleshooting. The Service period information is used for lifecycle and maintenance planning, such as tracking service time, maintenance intervals, or component life indicators where supported, enabling preventive maintenance and reducing unexpected downtime. Therefore, Device Management supports viewing all four categories.



Which of the following are the user roles of Power Partner?

  1. Service manager of a rep office
  2. Startup engineer
  3. Inventory operations manager
  4. Project manager
  5. DOC
  6. Service engineer

Answer(s): A,B,C,D,E,F

Explanation:

Power Partner is Huawei Digital Power’s partner service platform used to support delivery, commissioning, maintenance, and service operations across the full lifecycle of a project. To match real project workflows, the platform defines multiple user roles that align with different responsibilities and permission scopes. A Startup engineer focuses on commissioning activities such as obtaining startup authorization, performing initial configuration, and completing functional verification. A Service engineer handles routine maintenance, inspections, troubleshooting, part replacement guidance, and closure of service cases. A Project manager coordinates delivery milestones, resource planning, and overall service execution to ensure acceptance criteria are met. An Inventory operations manager manages materials/parts flow, tracking, and availability to support timely repair and maintenance. The DOC (Delivery/Dispatch Operations Center) role supports centralized operations such as work order dispatching, progress supervision, and process compliance. A service manager of a representative office typically oversees regional service quality, governance, and authorization control, ensuring the right people have the right access and that services are delivered according to Huawei process requirements.



The NetEco can be deployed on any virtualization platform.

  1. True
  2. False

Answer(s): B

Explanation:

NetEco is an enterprise management application with specific runtime dependencies, including supported operating system versions, database/middleware compatibility, CPU/memory/storage requirements, and network/security prerequisites. Because of these dependencies, Huawei does not treat NetEco as “hypervisor-agnostic for any virtualization platform.” In practice, NetEco deployment in virtualized environments is supported only when the virtualization stack meets Huawei’s compatibility requirements, such as validated hypervisors/virtualization solutions, proper virtual hardware settings, and resource reservation rules to ensure stable performance (especially for alarm processing, historical data storage, and northbound integration tasks). If deployed on an unverified virtualization platform, issues may occur such as clock drift, I/O latency, database performance bottlenecks, unstable NIC behavior, or unsupported VM device models, which can impact data collection, event correlation, and overall system stability. Therefore, the correct interpretation is that NetEco can be deployed on supported/verified virtualization platforms, not on any virtualization platform.



The software installation package does not need to be downloaded for the preinstalled server.

  1. True
  2. False

Answer(s): A

Explanation:

In Huawei delivery scenarios, a preinstalled server means the target software (for example, the NetEco platform and its required runtime components) has already been deployed and integrated on the server image before it is handed over for on-site commissioning. Because the installation media has already been applied, the on-site engineer’s work typically shifts from “software installation” to “environment verification and initialization,” such as confirming OS/service status, checking resource allocation, validating database and middleware health, verifying network planning (IP, gateway, DNS/NTP as required), and completing application-level initialization (site creation, user/role configuration, northbound interface settings, and device/model import if needed). In this case, downloading the full installation package is not a mandatory step for commissioning, because the package is mainly required when performing a fresh installation or reinstall/upgrade. However, standard practice is still to prepare supporting materials (patches, licenses, and compatibility documents) and ensure the preinstalled version matches the project baseline before acceptance.



The default port number for logging in to the NetEco is

  1. 32804
  2. 32805
  3. 31943
  4. 31945

Answer(s): C

Explanation:

In Huawei NetEco access design, the Web client is reached using HTTPS to protect credentials and management data in transit. During initial deployment and commissioning, engineers access the NetEco login page by entering the server IP address followed by the default HTTPS service port. Huawei’s standard login method specifies that users open a browser and enter https://NetEco server IP:31943 to access the NetEco login interface. This port is therefore treated as the default Web login port in typical on-premises NetEco deployments, and it is the baseline value referenced in installation and login guidance. Other ports may appear in specific tools, customized scenarios, version variants, reverse-proxy deployments, or when security policy requires port changes, but those are exceptions driven by planning or product packaging. For exam and commissioning purposes, the correct default login port is the one used by the NetEco Web client entry point under the standard deployment model: 31943.



Share your comments for Huawei H20-923_V1.0 exam with other users:

K
Kris
7/7/2023 9:43:00 AM

good morning, could you please upload this exam again, i need it to test my knowledge in sd-wan with version 7.0.

M
Meghraj mali
10/7/2023 1:47:00 PM

very nice question

N
Noel
11/1/2022 9:14:00 PM

i have learning disability and this exam dumps allowed me to focus on the actual questions and not worry about notes and the those other study materials.

J
Jas
10/25/2023 6:01:00 PM

165 should be apt

N
Neetu
6/22/2023 8:41:00 AM

please upload the dumps, real need of them

M
Mark
10/24/2023 1:34:00 AM

any recent feeedback?

G
Gopinadh
8/9/2023 4:05:00 AM

question number 2 is indicating you are giving proper questions. observe and change properly.

S
Santhi
1/1/2024 8:23:00 AM

passed today.40% questions were new.litwere case study,lots of new questions on afd,ratelimit,tm,lb,app gatway.got 2 set series of questions which are not present here.questions on azure cyclecloud, no.of vnet/vms required for implimentation,blueprints assignment/management group etc

R
Raviraj Magadum
1/12/2024 11:39:00 AM

practice test

S
sivaramakrishnan
7/27/2023 8:12:00 AM

want the dumps for emc content management server programming(cmsp)

A
Aderonke
10/23/2023 1:52:00 PM

brilliant and helpful

A
Az
9/16/2023 2:43:00 PM

q75. azure files is pass

K
ketty
11/9/2023 8:10:00 AM

very helpful

S
Sonail
5/2/2022 1:36:00 PM

thank you for these questions. it helped a lot.

S
Shariq
7/28/2023 8:00:00 AM

how do i get the h12-724 dumps

A
adi
10/30/2023 11:51:00 PM

nice data dumps

E
EDITH NCUBE
7/25/2023 7:28:00 AM

answers are correct

R
Raja
6/20/2023 4:38:00 AM

good explanation

B
BigMouthDog
1/22/2022 8:17:00 PM

hi team just want to know if there is any update version of the exam 350-401

F
francesco
10/30/2023 11:08:00 AM

helpful on 2017 scrum guide

A
Amitabha Roy
10/5/2023 3:16:00 AM

planning to attempt for the exam.

P
Prem Yadav
7/29/2023 6:20:00 AM

pleaseee upload

A
Ahmed Hashi
7/6/2023 5:40:00 PM

thanks ly so i have information cia

M
mansi
5/31/2023 7:58:00 AM

hello team, i need sap qm dumps for practice

J
Jamil aljamil
12/4/2023 4:47:00 AM

it’s good but not senatios based

C
Cath
10/10/2023 10:19:00 AM

q.119 - the correct answer is b - they are not captured in an update set as theyre data.

P
P
1/6/2024 11:22:00 AM

good matter

S
surya
7/30/2023 2:02:00 PM

please upload c_sacp_2308

S
Sasuke
7/11/2023 10:30:00 PM

please upload the dump. thanks very much !!

V
V
7/4/2023 8:57:00 AM

good questions

T
TTB
8/22/2023 5:30:00 AM

hi, could you please update the latest dump version

T
T
7/28/2023 9:06:00 PM

this question is keep repeat : you are developing a sales application that will contain several azure cloud services and handle different components of a transaction. different cloud services will process customer orders, billing, payment, inventory, and shipping. you need to recommend a solution to enable the cloud services to asynchronously communicate transaction information by using xml messages. what should you include in the recommendation?

G
Gurgaon
9/28/2023 4:35:00 AM

great questions

W
wasif
10/11/2023 2:22:00 AM

its realy good

AI Tutor 👋 I’m here to help!