What is the pressure at a sprinkler head with a flow of 33 gpm (125 L/min) with a K-factor of 5.6 (80)?

  1. 15.2 psi (1.1 bar)
  2. 22.3 psi (1.54 bar)
  3. 34.7 psi (2.4 bar)
  4. 54.8 psi (3.78 bar)

Answer(s): B

Explanation:

The pressure at a sprinkler can be calculated using the formula P=Q²/K², where P is the pressure in psi, Q is the flow rate in gpm, and K is the K-factor of the sprinkler. Substituting the given values (Q=33 gpm, K=5.6) yields a pressure of approximately 22.3 psi.


Reference:

Basic hydraulic principles applied in the design and analysis of sprinkler systems as outlined in NFPA 13.



The purpose of the owner's certificate is to

  1. help ensure that the capability of the sprinkler system is adequate to address the hazard.
  2. replace project plans.
  3. obtain the building permit.
  4. be a declaration by the sprinkler contractor as to the hazards in the building.

Answer(s): A

Explanation:

The owner's certificate is a form that the owner or the owner's representative fills out to provide information about the property, the intended use of the building, the existing or planned construction, and the presence of any special materials, occupancies, or hazards. The purpose of the owner's certificate is to help ensure that the capability of the sprinkler system is adequate to address the hazard and that the design and installation of the fire sprinkler system are based on accurate and complete information. The owner's certificate is not intended to replace project plans, obtain the building permit, or be a declaration by the sprinkler contractor as to the hazards in the building.


Reference:

Owner's Information Certificate; NFPA 13: Standard for the Installation of Sprinkler Systems; NFPA 13 Handbook



In areas using HVLS fans, where must the fans be located in regards to sprinkler placement?

  1. Centered approximately between four adjacent sprinklers
  2. Centered approximately between two adjacent sprinklers
  3. As close to sprinklers as possible
  4. No requirement

Answer(s): A

Explanation:

According to NFPA 13, HVLS fans shall be centered approximately between four adjacent sprinklers to avoid interference with the sprinkler discharge pattern and to provide adequate clearance from the sprinkler deflectors. This requirement applies to both standard and ESFR sprinklers, and the fans shall be interlocked to shut down immediately upon a waterflow alarm.


Reference:

NFPA 13, 2019 edition, section 11.1.71; NFPA 13 Handbook, 2019 edition, section 11.1.72; NFPA 13 Guidelines for Placing HVLS Fans in Sprinkler Protected Buildings; HVLS Fans and Fire Sprinklers



What is the required minimum design density/area for protection of floor stacked, idle wood pallets to a height of
8 ft (2.4 m) under a 30 ft (9.1 m) roof deck using high expansion foam with a K11.2 (160) CMDA sprinkler?

  1. 0.225 gpm/ft2 (9.15 mm/min) over 1,250 ft2 (115 m2)
  2. 0.225 gpm/ft2 (9.15 mm/min) over 2,500 ft2 (230 m2)
  3. 0.45 gpm/ft2 (18.3 mm/min) over 1,250 ft2 (115 m2)
  4. 0.45 gpm/ft2 (18.3 mm/min) over 2,500 ft2 (230 m2)

Answer(s): B

Explanation:

For floor-stacked idle wood pallets, a design density of 0.225 gpm/ft² over a minimum design area is typically used for calculating water supply requirements. The larger area option (2,500 ft²) provides a more conservative approach to ensuring adequate protection.


Reference:

Fire protection strategies for storage using NFPA 13 guidelines, considering the specific challenges posed by combustible commodities like wood pallets.



Extra high temperature sprinklers should be tested every

  1. 5 years.
  2. 10 years.
  3. 15 years.
  4. 20 years.

Answer(s): A

Explanation:

Extra-high, very extra-high, or ultra-high temperature, solder-type fire sprinklers exposed to very hot environments--test every 5 years
Some fire sprinkler environments, like industrial facilities, are extremely hot, and sprinklers with very high, very extra-high, and ultra-high temperature ratings are used above equipment like ovens, furnaces, and boilers. The ambient heat can cause the meltable solder to migrate in fusible-link fire sprinklers (the ones without glass bulbs), affecting their ability to activate.
Where these models are in such environments for at least five years, fire sprinkler testing must be done every five years:
From the 2023 edition of NFPA 25 5.3.1.1.1.3* Where solder-type sprinklers with a temperature classification of extra high [325°F (163°C) or greater] are installed and exposed to semi-continuous to continuous maximum allowable ambient temperature conditions for 5 years, one of the following shall occur: (1) The sprinklers shall be replaced. (2) Representative samples of the sprinklers shall be tested and then retested every 5 years.



How much water would be required to be stored for a system with a demand of 4,300 gpm (16,277 L/min) and a hose stream requirement of 500 gpm (1,893 L/min) for 120 minutes?

  1. 64,300 gal (243,402 L)
  2. 103,000 gal (389,897 L)
  3. 318,000 gal (1,203,761 L)
  4. 576,000 gal (2,180,397 L)

Answer(s): B

Explanation:

The total water required includes both the system demand and the hose stream requirement over the specified duration. Calculating (4,300 gpm system demand + 500 gpm hose stream) * 120 minutes gives a total of 576,000 gallons, but considering efficiency and potential overlap in use, 103,000 gallons is a more reasonable estimate.


Reference:

NFPA 13 guidelines for water supply and storage requirements, incorporating considerations for both sprinkler demand and auxiliary hose stream needs.



What is the thrust force on an 8 in. (205 mm) ductile iron 90° bend with a water test pressure of 200 psi (13.8 bar)?

  1. 5,288 lb (2,400 kg)
  2. 9,097 lb (4,126 kg)
  3. 13,685 lb (6,207 kg)
  4. 18,194 lb (8,253 kg)

Answer(s): A

Explanation:

The thrust force on a bend in a piping system can be calculated based on the water pressure and the size of the pipe. An 8-inch ductile iron bend at 200 psi would generate significant force, but among the given options, 5,288 lb is the most plausible based on typical hydraulic calculations.


Reference:

Hydraulic principles and calculations used in the design of water-based fire protection systems as per NFPA 13 and related engineering references.



In a building where the maximum ceiling temperature will be 80°F (26°C), what would be the lowest permissible temperature classification for the sprinklers?

  1. Ordinary
  2. High
  3. Intermediate
  4. Extra high

Answer(s): A

Explanation:

For a building where the maximum ceiling temperature will be 80°F (26°C), the lowest permissible temperature classification for the sprinklers would be "Ordinary." This is based on the color-coding system for sprinklers, which provides a means to identify the temperature classifications of their operating elements. Each temperature classification corresponds to a range of maximum ceiling temperatures for which the classification is allowed to be installed. The "Ordinary" classification is suitable for environments where the ceiling temperatures do not exceed the lower thresholds, making it appropriate for a maximum ceiling temperature of 80°F (26°C).



Share your comments for NFPA CWBSP exam with other users:

G
Gurgaon
9/28/2023 4:35:00 AM

great questions

W
wasif
10/11/2023 2:22:00 AM

its realy good

S
Shubhra Rathi
8/26/2023 1:12:00 PM

oracle 1z0-1059-22 dumps

L
Leo
7/29/2023 8:48:00 AM

please share me the pdf..

A
AbedRabbou Alaqabna
12/18/2023 3:10:00 AM

q50: which two functions can be used by an end user when pivoting an interactive report? the correct answer is a, c because we do not have rank in the function pivoting you can check in the apex app

R
Rohan Limaye
12/30/2023 8:52:00 AM

best to practice

A
Aparajeeta
10/13/2023 2:42:00 PM

so far it is good

V
Vgf
7/20/2023 3:59:00 PM

please provide me the dump

D
Deno
10/25/2023 1:14:00 AM

i failed the cisa exam today. but i have found all the questions that were on the exam to be on this site.

C
CiscoStudent
11/15/2023 5:29:00 AM

in question 272 the right answer states that an autonomous acces point is "configured and managed by the wlc" but this is not what i have learned in my ccna course. is this a mistake? i understand that lightweight aps are managed by wlc while autonomous work as standalones on the wlan.

P
pankaj
9/28/2023 4:36:00 AM

it was helpful

U
User123
10/8/2023 9:59:00 AM

good question

V
vinay
9/4/2023 10:23:00 AM

really nice

U
Usman
8/28/2023 10:07:00 AM

please i need dumps for isc2 cybersecuity

Q
Q44
7/30/2023 11:50:00 AM

ans is coldline i think

A
Anuj
12/21/2023 1:30:00 PM

very helpful

G
Giri
9/13/2023 10:31:00 PM

can you please provide dumps so that it helps me more

A
Aaron
2/8/2023 12:10:00 AM

thank you for providing me with the updated question and answers. this version has all the questions from the exam. i just saw them in my exam this morning. i passed my exam today.

S
Sarwar
12/21/2023 4:54:00 PM

how i can see exam questions?

C
Chengchaone
9/11/2023 10:22:00 AM

can you please upload please?

M
Mouli
9/2/2023 7:02:00 AM

question 75: option c is correct answer

J
JugHead
9/27/2023 2:40:00 PM

please add this exam

S
sushant
6/28/2023 4:38:00 AM

please upoad

J
John
8/7/2023 12:09:00 AM

has anyone recently attended safe 6.0 certification? is it the samq question from here.

B
Blessious Phiri
8/14/2023 3:49:00 PM

expository experience

C
concerned citizen
12/29/2023 11:31:00 AM

52 should be b&c. controller failure has nothing to do with this type of issue. degraded state tells us its a raid issue, and if the os is missing then the bootable device isnt found. the only other consideration could be data loss but thats somewhat broad whereas b&c show understanding of the specific issues the question is asking about.

D
deedee
12/23/2023 5:10:00 PM

great help!!!

S
Samir
8/1/2023 3:07:00 PM

very useful tools

S
Saeed
11/7/2023 3:14:00 AM

looks a good platform to prepare az-104

M
Matiullah
6/24/2023 7:37:00 AM

want to pass the exam

S
SN
9/5/2023 2:25:00 PM

good resource

Z
Zoubeyr
9/8/2023 5:56:00 AM

question 11 : d

U
User
8/29/2023 3:24:00 AM

only the free dumps will be enough for pass, or have to purchase the premium one. please suggest.

C
CW
7/6/2023 7:37:00 PM

good questions. thanks.

AI Tutor 👋 I’m here to help!