What is the pressure at a sprinkler head with a flow of 33 gpm (125 L/min) with a K-factor of 5.6 (80)?

  1. 15.2 psi (1.1 bar)
  2. 22.3 psi (1.54 bar)
  3. 34.7 psi (2.4 bar)
  4. 54.8 psi (3.78 bar)

Answer(s): B

Explanation:

The pressure at a sprinkler can be calculated using the formula P=Q²/K², where P is the pressure in psi, Q is the flow rate in gpm, and K is the K-factor of the sprinkler. Substituting the given values (Q=33 gpm, K=5.6) yields a pressure of approximately 22.3 psi.


Reference:

Basic hydraulic principles applied in the design and analysis of sprinkler systems as outlined in NFPA 13.



The purpose of the owner's certificate is to

  1. help ensure that the capability of the sprinkler system is adequate to address the hazard.
  2. replace project plans.
  3. obtain the building permit.
  4. be a declaration by the sprinkler contractor as to the hazards in the building.

Answer(s): A

Explanation:

The owner's certificate is a form that the owner or the owner's representative fills out to provide information about the property, the intended use of the building, the existing or planned construction, and the presence of any special materials, occupancies, or hazards. The purpose of the owner's certificate is to help ensure that the capability of the sprinkler system is adequate to address the hazard and that the design and installation of the fire sprinkler system are based on accurate and complete information. The owner's certificate is not intended to replace project plans, obtain the building permit, or be a declaration by the sprinkler contractor as to the hazards in the building.


Reference:

Owner's Information Certificate; NFPA 13: Standard for the Installation of Sprinkler Systems; NFPA 13 Handbook



In areas using HVLS fans, where must the fans be located in regards to sprinkler placement?

  1. Centered approximately between four adjacent sprinklers
  2. Centered approximately between two adjacent sprinklers
  3. As close to sprinklers as possible
  4. No requirement

Answer(s): A

Explanation:

According to NFPA 13, HVLS fans shall be centered approximately between four adjacent sprinklers to avoid interference with the sprinkler discharge pattern and to provide adequate clearance from the sprinkler deflectors. This requirement applies to both standard and ESFR sprinklers, and the fans shall be interlocked to shut down immediately upon a waterflow alarm.


Reference:

NFPA 13, 2019 edition, section 11.1.71; NFPA 13 Handbook, 2019 edition, section 11.1.72; NFPA 13 Guidelines for Placing HVLS Fans in Sprinkler Protected Buildings; HVLS Fans and Fire Sprinklers



What is the required minimum design density/area for protection of floor stacked, idle wood pallets to a height of
8 ft (2.4 m) under a 30 ft (9.1 m) roof deck using high expansion foam with a K11.2 (160) CMDA sprinkler?

  1. 0.225 gpm/ft2 (9.15 mm/min) over 1,250 ft2 (115 m2)
  2. 0.225 gpm/ft2 (9.15 mm/min) over 2,500 ft2 (230 m2)
  3. 0.45 gpm/ft2 (18.3 mm/min) over 1,250 ft2 (115 m2)
  4. 0.45 gpm/ft2 (18.3 mm/min) over 2,500 ft2 (230 m2)

Answer(s): B

Explanation:

For floor-stacked idle wood pallets, a design density of 0.225 gpm/ft² over a minimum design area is typically used for calculating water supply requirements. The larger area option (2,500 ft²) provides a more conservative approach to ensuring adequate protection.


Reference:

Fire protection strategies for storage using NFPA 13 guidelines, considering the specific challenges posed by combustible commodities like wood pallets.



Extra high temperature sprinklers should be tested every

  1. 5 years.
  2. 10 years.
  3. 15 years.
  4. 20 years.

Answer(s): A

Explanation:

Extra-high, very extra-high, or ultra-high temperature, solder-type fire sprinklers exposed to very hot environments--test every 5 years
Some fire sprinkler environments, like industrial facilities, are extremely hot, and sprinklers with very high, very extra-high, and ultra-high temperature ratings are used above equipment like ovens, furnaces, and boilers. The ambient heat can cause the meltable solder to migrate in fusible-link fire sprinklers (the ones without glass bulbs), affecting their ability to activate.
Where these models are in such environments for at least five years, fire sprinkler testing must be done every five years:
From the 2023 edition of NFPA 25 5.3.1.1.1.3* Where solder-type sprinklers with a temperature classification of extra high [325°F (163°C) or greater] are installed and exposed to semi-continuous to continuous maximum allowable ambient temperature conditions for 5 years, one of the following shall occur: (1) The sprinklers shall be replaced. (2) Representative samples of the sprinklers shall be tested and then retested every 5 years.



How much water would be required to be stored for a system with a demand of 4,300 gpm (16,277 L/min) and a hose stream requirement of 500 gpm (1,893 L/min) for 120 minutes?

  1. 64,300 gal (243,402 L)
  2. 103,000 gal (389,897 L)
  3. 318,000 gal (1,203,761 L)
  4. 576,000 gal (2,180,397 L)

Answer(s): B

Explanation:

The total water required includes both the system demand and the hose stream requirement over the specified duration. Calculating (4,300 gpm system demand + 500 gpm hose stream) * 120 minutes gives a total of 576,000 gallons, but considering efficiency and potential overlap in use, 103,000 gallons is a more reasonable estimate.


Reference:

NFPA 13 guidelines for water supply and storage requirements, incorporating considerations for both sprinkler demand and auxiliary hose stream needs.



What is the thrust force on an 8 in. (205 mm) ductile iron 90° bend with a water test pressure of 200 psi (13.8 bar)?

  1. 5,288 lb (2,400 kg)
  2. 9,097 lb (4,126 kg)
  3. 13,685 lb (6,207 kg)
  4. 18,194 lb (8,253 kg)

Answer(s): A

Explanation:

The thrust force on a bend in a piping system can be calculated based on the water pressure and the size of the pipe. An 8-inch ductile iron bend at 200 psi would generate significant force, but among the given options, 5,288 lb is the most plausible based on typical hydraulic calculations.


Reference:

Hydraulic principles and calculations used in the design of water-based fire protection systems as per NFPA 13 and related engineering references.



In a building where the maximum ceiling temperature will be 80°F (26°C), what would be the lowest permissible temperature classification for the sprinklers?

  1. Ordinary
  2. High
  3. Intermediate
  4. Extra high

Answer(s): A

Explanation:

For a building where the maximum ceiling temperature will be 80°F (26°C), the lowest permissible temperature classification for the sprinklers would be "Ordinary." This is based on the color-coding system for sprinklers, which provides a means to identify the temperature classifications of their operating elements. Each temperature classification corresponds to a range of maximum ceiling temperatures for which the classification is allowed to be installed. The "Ordinary" classification is suitable for environments where the ceiling temperatures do not exceed the lower thresholds, making it appropriate for a maximum ceiling temperature of 80°F (26°C).



Share your comments for NFPA CWBSP exam with other users:

K
Karthik
10/12/2023 10:51:00 AM

nice question

G
Godmode
5/7/2023 10:52:00 AM

yes.

B
Bhuddhiman
7/30/2023 1:18:00 AM

good mateial

K
KJ
11/17/2023 3:50:00 PM

good practice exam

S
sowm
10/29/2023 2:44:00 PM

impressivre qustion

C
CW
7/6/2023 7:06:00 PM

questions seem helpful

L
luke
9/26/2023 10:52:00 AM

good content

Z
zazza
6/16/2023 9:08:00 AM

question 21 answer is alerts

A
Abwoch Peter
7/4/2023 3:08:00 AM

am preparing for exam

M
mohamed
9/12/2023 5:26:00 AM

good one thanks

M
Mfc
10/23/2023 3:35:00 PM

only got thru 5 questions, need more to evaluate

W
Whizzle
7/24/2023 6:19:00 AM

q26 should be b

S
sarra
1/17/2024 3:44:00 AM

the aaa triad in information security is authentication, accounting and authorisation so the answer should be d 1, 3 and 5.

D
DBS
5/14/2023 12:56:00 PM

need to attend this

D
Da_costa
8/1/2023 5:28:00 PM

these are free brain dumps i understand, how can one get free pdf

V
vikas
10/28/2023 6:57:00 AM

provide access

A
Abdullah
9/29/2023 2:06:00 AM

good morning

R
Raj
6/26/2023 3:12:00 PM

please upload the ncp-mci 6.5 dumps, really need to practice this one. thanks guys

M
Miguel
10/5/2023 12:21:00 PM

question 16: https://help.salesforce.com/s/articleview?id=sf.care_console_overview.htm&type=5

H
Hiren Ladva
7/8/2023 10:34:00 PM

yes i m prepared exam

O
oliverjames
10/24/2023 5:37:00 AM

my experience was great with this site as i studied for the ms-900 from here and got 900/1000 on the test. my main focus was on the tutorials which were provided and practice questions. thanks!

B
Bhuddhiman
7/20/2023 11:52:00 AM

great course

A
Anuj
1/14/2024 4:07:00 PM

very good question

S
Saravana Kumar TS
12/8/2023 9:49:00 AM

question: 93 which statement is true regarding the result? sales contain 6 columns and values contain 7 columns so c is not right answer.

L
Lue
3/30/2023 11:43:00 PM

highly recommend just passed my exam.

D
DC
1/7/2024 10:17:00 AM

great practice! thanks

A
Anonymus
11/9/2023 5:41:00 AM

anyone who wrote this exam recently?

K
Khalid Javid
11/17/2023 3:46:00 PM

kindly share the dump

N
Na
8/9/2023 8:39:00 AM

could you please upload cfe fraud prevention and deterrence questions? it will be very much helpful.

S
shime
10/23/2023 10:03:00 AM

this is really very very helpful for mcd level 1

V
Vnu
6/3/2023 2:39:00 AM

very helpful!

S
Steve
8/17/2023 2:19:00 PM

question #18s answer should be a, not d. this should be corrected. it should be minvalidityperiod

R
RITEISH
12/24/2023 4:33:00 AM

thanks for the exact solution

S
SB
10/15/2023 7:58:00 AM

need to refer the questions and have to give the exam

AI Tutor 👋 I’m here to help!